(H)07V-K 1X2,5 - BROWNWHITE | M0010362_5001831
Indoor
Oil resistant
CE CPR Class - Eca HAR
fixed installation
PVC insulated wiring cables

LIYvz, H05V-K, H07V-K

09.01.01

|

Application

LiYvz as switching strand for wiring telecommunication units, electrical modules in devices as well as telecommunication facilities. H05V-K and H07V-K as single core for internal wiring of devices as well as protected laying within and on shiners. Laying within pipes on-wall and in-wall permitted for signal facilities.

Selected item
Item no.: Description:
5001831 (H)07V-K 1X2,5 BROWNWHITE*
Variants
Filter
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
Filter

Filter according to your requirements.

fixed installation
LIYvz, H05V-K, H07V-K 1 X 4 5000157
PVC insulated wiring cables
300/500V, 450/750V, Hook-up wires, HAR, CPR Eca
UN/ECE-R 118.02
fixed installation
LIYvz, H05V-K, H07V-K 1 X 150 5000113
PVC insulated wiring cables
300/500V, 450/750V, Hook-up wires, HAR, CPR Eca
UN/ECE-R 118.02
fixed installation
LIYvz, H05V-K, H07V-K 1 X 25 5000144
PVC insulated wiring cables
300/500V, 450/750V, Hook-up wires, HAR, CPR Eca
UN/ECE-R 118.02
fixed installation
LIYvz, H05V-K, H07V-K 1 X 10 5000106
PVC insulated wiring cables
300/500V, 450/750V, Hook-up wires, HAR, CPR Eca
UN/ECE-R 118.02
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "LIYvz, H05V-K, H07V-K "
SPECIAL FEATURES
  • largely resistant to acids, alkalis and certain oils
  • LABS-free / silicone-free (during production)
  • self-extinguishing and flame-retardant
  • must not be used for direct laying on platforms, channels or trays (exception as potential equalization)
  • all common standard colors available
  • flame-retardant & tested in accordance with UN/ECE-R 118.02
REMARKS
  • RoHS compliant
  • comp. with 2014/35/EU Directive (''Low Voltage Directive'') CE
  • shielded PVC single core ELITRONIC ®-CY LIYCY see chapter 02.01.02
  • special versions, other dimensions, cross-sections, core and sheath colors are available on request
PRODUCT DETAILS
DESIGN
Conductor material LiYvz: copper strand tinned; H05V-K, H07V-K: bare copper strand
Conductor class acc. to IEC 60228 class 5
Core insulation PVC
Core identification different colours
ELECTRICAL PROPERTIES
Rated voltage AC IEC H05V-K: 300/500 V; H07V-K: 450/750 V peak voltage LiYvz 500 V (0,14mm²), 900 V (0,25mm²-1,5mm²)
Testing voltage LiYvz: 1,2 kV (0,14mm²), 2,5 kV (0,25mm²-1,5 mm²) H05V-K: 2 kV; H07V-K: 2,5 kV
Conductor resistance at +20 °C LiYvz acc. to VDE 0812; H05V-K and H07V-K acc. to IEC 60228
Current carrying capacity acc. to. DIN VDE, see Technical Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed LIYvz: 10 x d // H05/07V-K: OD < 8,0 mm = 3xd; OD < 12,0 mm = 3xd; OD > 12,0 mm = 4xd - careful curve near terminal: OD < 8,0 mm = 2xd; OD < 12,0 mm = 3xd; OD >12,0 mm = 4xd
Min. bending radius moved 15 x d
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -30 °C / +80 °C (HAR: +70 °C)
Operat. temp. moved min/max [°C] -5 °C / +70 °C
STANDARDS & APPROVALS
Standard LiYvz similar to VDE0812; H05/H07V-K: acc. to EN 50525-2-31 (IEC 60227-3)
Approvals H05V-K and H07V-K: HAR ; UN/ECE-R 118.02: DEKRA TR 202460181