Indoor
Shielded Oil resistant
CE CPR Class - Eca
fixed installation flexible use
Electronic and control cables for intrinsically safe circuits

ELITRONIC®-OZ-CY LIYCY-OZ EB

02.03.02

|

Application

exclusively for use in self-protective circuits, as impulse and data transmission cable, control and connecting cable in process controlled facilities in measurement and control technology for lossless data and signal transmission. For fixed laying and flexible applications with undefined cable routing and without tensile stress. Suitable for use in dry and humid rooms. Outdoor use only with UV-protection, no laying underground.

Selected item
Item no.: Description:
0500770 ELITRONIC-OZ-CY EB LIYCY-OZ 18X1,5 300/500 V, BLUE RAL 5015
Variants
Filter
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
Filter

Filter according to your requirements.

fixed installation flexible use
ELITRONIC®-CY LIYCY 18 X 1,5 0500554
Electronic cables
DIN47100, 250V, shielded, CPR Eca
UN/ECE-R 118.02
We recommend this product as a suitable alternative!
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "ELITRONIC®-OZ-CY LIYCY-OZ EB "
SPECIAL FEATURES
  • for intrinsically safe electric circuits
  • protection class "i" acc. to VDE 0165
  • largely resistant to acids, bases and specified types of oil
  • intrinsically safe systems are circuits where no spark and no thermic effect in normal operation or in failure can ignite explosive surrounding areas. These products are intended for use within <50 V AC resp. <75 V DC voltage. Therefore they are not subject to the EU Low Voltage Directive.
REMARKS
  • RoHS-compliant
  • LBS-free/silicon-free (during production)
  • Recommended for EMC-compliant application
  • Alternatively available: ÖPVC-JZ-YCY EB, ELITRONIC®-CY EB (DIN47100), PAARTRONIC®-CY EB LIYCY (TP) (DIN47100)
PRODUCT DETAILS
DESIGN
Conductor material bare copper strand
Conductor class acc. to IEC 60228 cl. 5
Core insulation PVC
Core identification acc. to DIN VDE 0293 black cores with white numerals but without GNYE
Stranding stranded in layers
Overall shield copper braid tinned; coverage approx. 85%
Outer sheath material PVC
Sheath colour blue, RAL 5015
ELECTRICAL PROPERTIES
Rated voltage AC IEC Uo/U: 300/500 V (see special features)
Testing voltage 3 kV
Conductor resistance acc. to IEC 60228 cl. 5
Insulation resistance min. 20 MΩ x km
Current carrying capacity acc. to DIN VDE, s. Techn. Guidelines
Capacity core/core ca. 120 nF/km; core/shield ca. 160 nF/km
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed up to 12 mm Ø 5 x d; > 12 mm Ø 7,5 x d
Min. bending radius moved up to 12 mm Ø 10 x d; up to 20 mm Ø 15 x d; > 20 mm Ø 20 x d
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -30 °C / +80 °C
Operat. temp. moved min/max [°C] -5 °C / +70 °C