ÖPVC-JB/OB-YSY | 1000796 | 1000796
PVC control cables

ÖPVC-JB/OB-YSY

01.01.07

|

Use of Cable

power, control and connecting cable in electrical facilities, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use only with UV-protection, no laying underground.

Product variants
Product information "ÖPVC-JB/OB-YSY"
Special features
  • 4 kV testing voltage
  • no storage outdoors or in wet rooms 
  • JZ/OZ: 300/500 V, JB/OB: 0,6/1 kV (from 25 mm²) 
  • largely resistant to acids, bases and specified types of oil 
  • triple protection for high mechanical requirements and magnetic shield (oxidation-proofed steel wire braid and additional inner sheath)
Remarks
  • conform to RoHS
  • conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
  • LABS-/silicone-free (during production)
  • We are pleased to produce special versions, other dimensions, core and jacket colours on request
Conductor material: Bare copper strand
Conductor class: Acc. to IEC 60228 cl. 5
Core insulation: PVC
Core identification: JZ/OZ: acc. to DIN VDE 0293 black cores with white numerals; JB/OB: coloured - up to 5 cores acc. to DIN 293-308, from 6 cores TKD colour code (see technical guideline) G: with GNYE
Stranding: Stranded in layers
Inner sheath material: PVC
Shield3: Steel wire braid zinced
Outer sheath: PVC
Sheath colour: Transparent
Rated voltage: Uo/U - JZ/OZ: 300/500 V || JB/OB: 0,6/1 kV
Testing voltage: 4 kV
Conductor resistance: Acc. to IEC 60228 cl. 5
Insulation resistance: Min. 20 MΩ x km
Current-carrying-capacity: Acc. to DIN VDE, see technical Guidelines
Min. bending radius fixed: 6 x d
Min. bending radius moved: 15 x d
Operat. temp. fixed min/max: -30 °C / +80 °C
Operat. temp. moved min/max: -15 °C / +70 °C
Temp. at conductor: +70 °C in operation; +150 °C in case of short-circuit
Burning behavior: Self-extinguishing & flame-retardant acc.to IEC 60332-1
Standard: Similar to EN 50525-2-51| 0,6/1 kV-type: with insulation thickness for 1 kV

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.

There aren't any asked questions yet.
ÖPVC-JZ/OZ ARCTIC +UV BLACK 01.01.04.05
PVC control cables
300/500V, unshielded, cold resistant -60°C
Item count 89
ÖPVC-JZ/OZ 01.01.04
PVC control cables
300/500V, unshielded, CPR Eca
Item count 195
ÖPVC-OZ-Yö 1.000 V 01.01.04.02
PVC control cables
450/750V (IEC), 1.000V (UL), unshielded UL/CSA
Item count 135
ÖPVC-JZ/OZ-CY (LIYCY-JZ/OZ) 01.01.06
PVC control cables
300/500V, shielded, CPR Eca
Item count 114