Silicone insulated cables up to +180°C
H05SS-F / H05SS-F EWKF
08.04.06
|
Use of Cable
harmonized heat and coldness resistant power, control and connecting cable in electrical facilities, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no laying underground.
Product information "H05SS-F / H05SS-F EWKF"
Special features
- approved for conductor temperature class "H" up to +180 °C
- no flame conduction in case of fire, insulation integrity and low smoke density
- silicone is resistant to ozone, oxygen, sea water and weather-proofed
- hydrolisis and UV-resistant / HAR approval for Europe
- EWKF-version: initial tear, tear growth & notch resistant
- above +100 °C and with exclusion of air, the mechanical properties of silicone cables
will be reduced early, adequate ventilation should be ensured
- conform to RoHS
- conform to 2014/35/EU-Guideline ("Low-Voltage Directive") CE
- We are pleased to produce special versions, other dimensions, core and jacket colours on request.
Conductor material: | Copper strand tinned |
---|---|
Conductor class: | Acc. to IEC 60228 cl. 5 |
Core insulation: | Silicone resp. silicone EWKF based |
Core identification: | Acc. to DIN VDE 0293-308 coloured cores |
Stranding: | Stranded in layers |
Outer sheath: | Silicone resp. silicone EWKF-based |
Sheath colour: | Black |
Rated voltage: | Uo/U: 300/500 V |
Testing voltage: | 2 kV |
Conductor resistance: | At +20 °C acc. to IEC 60228 cl. 5 |
Insulation resistance: | Min. 2,0 GΩ x km |
Current-carrying-capacity: | Acc. to DIN VDE, see Technical Guidelines |
Min. bending radius fixed: | 4 x d |
Min. bending radius moved: | 15 x d |
Operat. temp. fixed min/max: | -50 °C / +180 °C (with adequate aeration) |
Halogen free: | Halogen-free acc. to IEC 60754-1 |
Corrodibility: | Acc. to IEC 60754-2 |
Burning behavior: | Self-extinguishing and flame-retardant acc. to IEC 60332-1-2 |
Approvals: | EN 50525-2-83 (H05SS-F) |
There aren't any asked questions yet.
SiD, SiD/GL, SiF, SiF/GL, SiFF, SiFv, SiZ
08.04.01
Silicone insulated cables up to +180°C
300/500V, singles cores & twin cable, halogen-free, solid & fine stranded, GL:glass silk braid
300/500V, singles cores & twin cable, halogen-free, solid & fine stranded, GL:glass silk braid
Item count
273
SIHF-J
08.04.03
Silicone insulated cables up to +180°C
300/500V, unshielded, halogen-free, fine stranded
300/500V, unshielded, halogen-free, fine stranded
Item count
71