Silicone insulated cables up to +180°C
SIHF+C / SIHF-SI+C
08.04.04
|
heat and coldness resistant power, control and connecting cable in electrical facilities, for lossless data and signal transmission, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms and outdoor use, no laying underground.
Silicone insulated cables up to +180°C
Silicone insulated cables up to +180°C
Silicone insulated cables up to +180°C
Silicone insulated cables up to +180°C
Silicone insulated cables up to +180°C
SPECIAL FEATURES
- largely resistant to acids, bases and specified types of oil
- no flame conduction in case of fire, insulation integrity and low smoke density
- resistant to ozone and humidty, weather-proofed
- recommended for EMC-applications
- above +100 °C and with exclusion of air, the mechanical properties of silicone cables will be reduced early, adequate ventilation should be ensured
REMARKS
- RoHS compliant
- compliant with 2014/35/EU Directive (''Low Voltage Directive'') CE
- SIHF-SI+C: with inner sheath
- Special versions, other dimensions, cross-sections, core and sheath colors are available on request.
PRODUCT DETAILS
DESIGN
| Conductor material | copper strand tinned |
|---|---|
| Conductor class | acc. to IEC 60228 cl. 5 |
| Core insulation | silicone |
| Core identification | up to 5 cores acc. to DIN VDE 0293-308 coloured cores; from 6 cores black cores with white numerals with or without GNYE |
| Stranding | stranded in layers |
| Inner sheath material | SIHF-SI+C: silicone |
| Inner sheath colour | redbrown |
| Overall shield | copper braid tinned; coverage appr. 85% |
| Outer sheath material | silicone |
| Sheath colour | redbrown |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | Uo/U: 300/500 V |
|---|---|
| Testing voltage | 2 kV; core/shield: 1 kV |
| Conductor resistance | at +20 °C acc. to IEC 60228 cl. 5 |
| Insulation resistance | min. 2,0 GΩ x km |
| Current carrying capacity | acc. to DIN VDE, see Technical Guidelines |
MECHANICAL & DYNAMIC PROPERTIES
| Min. bending radius fixed | 5 x d |
|---|---|
| Min. bending radius moved | 12 x d |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -60 °C / +180 °C; short-time: +200 °C |
|---|---|
| Temp. at conductor in operation max [°C] | +180 °C |
PROPERTIES IN CASE OF FIRE
| Halogen-free | halogen-free acc. to IEC 60754-1 |
|---|---|
| Corrodibility | acc. to IEC 60754-2 |
| Burning behavior | self-extinguishing and flame-retardant acc. to IEC 60332-1-2 |