BUS | FIELDBUS cables for industrial & process automation
PROFIBUS DP / FMS / FIP 150 Ohm - HF UL/CSA -high flexible -
03.10.01.02
|
as fieldbus cables for PROFIBUS (Process Field BUS) systems, for highly flexible applications (e.g. energy guiding chains, gantry robots, pick&place units, conveyor systems, machine tools, automatic production systems, manufacturing systems etc.)
The cables are suitable for PROFIBUS DP (Decentral Periphery), PROFIBUS FMS (Fieldbus Message Specification) as well as FIP (Factory Instrumentation Protocol). Standard according to Profibus specification: EN61158 & EN61784 (DIN19245 T3 & EN50170)
Filter according to your requirements.
BUS | FIELDBUS cables for industrial & process automation
SPECIAL FEATURES
- low adhesion
- largely resistant to grease, coolants and lubricants
- oil-resistant: PUR & PVC acc. DIN EN 60811-2-1 (PVC only mineral oil)
- UV-resistant
- optimized EMC-compliant shielding
- max. cable length of a bus according to PNO at specified transmission rate:
| PROFIBUS DP | FIP | ||||
| 93,7 kbit/s | max. 1,2km | 2,5 Mbit/s | max. 200m | ||
| 187,5 kbit/s | max. 1,0km | ||||
| 0,5 Mbit/s | max. 400m | ||||
| 1,5 Mbit/s | max. 200m | ||||
| 12,0 Mbit/s | max. 100m |
REMARKS
- RoHS-compliant // DESINA-compliant (violet)
- LABS/silicone-free (during production)
- compliant to the 2014/35/EU Directive (''Low Voltage Directive'') CE
- FRNC: Flame Retardant Non Corrosive, halogen-free
- FC type with 'fast-connect' cable construction // PNO = PROFIBUS Nutzerorganisation e.V.
PRODUCT DETAILS
DESIGN
| Conductor material | bare copper strand |
|---|---|
| Conductor class | Ø 0,64L & 0,34 mm²: 19-wired; 1,0 mm²: fine wired acc. to IEC 60228 cl. 6 |
| Core insulation | BUS: foamed PE/PP; supply cores: Polyolefin |
| Core identification | BUS: gn, rd; supply cores: bk, bu, gnye (1,0mm²) | bk with numerals (1,5mm²) |
| Stranding | BUScores stranded to a pair |
| Element shielding | alu-lam. polyester foil, metal side outside, coverage 100% under copper braid tinned |
| Overall stranding | HYBRID: screened BUSelem. a. supply cores stranded |
| Outer sheath material | PVC resp. PUR |
| Sheath colour | violet RAL 4001 (VT) or petrol (PT) |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | BUScores: 250 V (not for high voltage purposes); supply cores: 500 V |
|---|---|
| Loop resistance | max. 133,0 Ω/km-0,64L & 0,8L, max. 39,0 Ω/km-1 mm², max. 26,6 Ω/km-1,5 mm² |
| Capacity | nom. 30 nF/km |
| Characteristic impedance | 150 +/- 15 Ω |
MECHANICAL & DYNAMIC PROPERTIES
| Min. bending radius fixed | 5 x d |
|---|---|
| Min. bending radius moved | 7,5 x d < 3mTL* | 15 x d ≥ 3mTL*, FESTOON: 10 x d |
| Traverse length (m) - drag chain | max. 10 m (TL) |
| Traverse speed (m/s) - drag chain | self-supporting: 4 m/s |
| Acceleration (m/s²) - drag chain | max. 5 m/s² | TORSION: max. 10 m/s² |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -40 °C / +80 °C |
|---|---|
| Operat. temp. moved min/max [°C] | PVC: -10 °C / +70 °C; PUR: -30 °C/ +70 °C |
PROPERTIES IN CASE OF FIRE
| Halogen-free | acc. to IEC 60754-1 (FRNC types) |
|---|---|
| Burning behavior | PVC CMG: acc. IEC 60332-3-24(Cat.C), FT 4 | PUR: acc. IEC 60332-1-2 | PUR CMX: acc. IEC 60332-1-2, VW-1 |