NYCY 0,6/1KV 1X25 RM/25 - BLACK RAL 9005 | M0011441_4000808
Indoor Outdoor Direct burial
Shielded UV-resistant
CE CPR Class - Eca VDE
fixed installation
Power Cables

NYCY 0,6/1kV

09.07.02

|

Application

power cable for use in generating plants, industrial facilities, switching stations, in local networks and power supply industry. Use predominantly for laying underground, indoor- and outdoor use, cable channels and in water when increased mechanical protection resp. contact protection in case of failure is required.

Selected item
Item no.: Description:
4000808 NYCY 0,6/1KV 1X25 RM/25 BLACK RAL 9005
Variants
Filter
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
fixed installation
NAYY 0,6/1kV 1 X 70rm 4001400
Power Cables
0,6/1kV, AL-Leiter, UV-resistant, direct burial, VDE, CPR Eca
fixed installation
NYY 0,6/1kV 1 X 150rm 4000202
Power Cables
0,6/1kV, UV-resistant, direct burial, VDE, CPR Eca
fixed installation
NAYY 0,6/1kV 1 X 500rm 4001409
Power Cables
0,6/1kV, AL-Leiter, UV-resistant, direct burial, VDE, CPR Eca
fixed installation
NYY 0,6/1kV 1 X 300rm 4000214
Power Cables
0,6/1kV, UV-resistant, direct burial, VDE, CPR Eca
fixed installation
NYY 0,6/1kV 1 X 10re 4000199
Power Cables
0,6/1kV, UV-resistant, direct burial, VDE, CPR Eca
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "NYCY 0,6/1kV "
SPECIAL FEATURES
  • 0,6/1 kV operating voltage, 4 kV testing voltage
  • UV-resistant
  • no hood termination necessary when laying in dry rooms
  • use of concentric conductor as shield, neutral conductor or earth conductor is permitted but not as outer conductor
  • free from lacquer damaging substances and silicone (during production)
REMARKS
  • RoHS compliant
  • compliant with 2006/95/EC Directive ("Low Voltage Directive") CE.
  • available with blue outer sheath for intrinsically safe systems on request
  • Special versions, other dimensions, cross-sections, core and sheath colors are available on request
PRODUCT DETAILS
DESIGN
Conductor material bare copper conductor
Conductor class acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
Core insulation PVC
Core identification single core black; multi core acc. to VDE 0207 part 4
Stranding multi core stranded in layers
Inner sheath material filler sheath
Overall shield concentric conductor of blank round copper wires
Outer sheath material PVC
Sheath colour black
ELECTRICAL PROPERTIES
Rated voltage AC IEC Uo/U: 0,6/1 kV
Testing voltage 4 kV
Conductor resistance at +20 °C acc. to DIN VDE 0295 class 1 resp. IEC 60228 cl. 1
Current carrying capacity acc. to DIN VDE, see Technical Guidelines
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40 °C / +70 °C
Operat. temp. moved min/max [°C] - 5 °C / +50 °C
Temp. at conductor in operation max [°C] + 70 °C in operation; +160 °C in case of short-circuit
STANDARDS & APPROVALS
Standard acc. to DIN VDE 0276-603 and IEC 60502
Approvals VDE