MULTIBUS SK-C-PUR FRNC UL/CSA 2X2X0,25 - VIOLET, cULus CMX | M0006068_2003666
Indoor Outdoor
Shielded UV-resistant Oil resistant Halogen-free
CE CSA
fixed installation flexible use continuously dynamic, high flexible use Drag chain
BUS | FIELDBUS cables for industrial & process automation

MULTIBUS & INTERBUS 100 - 120 Ohm - HF UL/CSA -high flexible -

03.10.02.02

|

Application

MULTIBUS - as fieldbus cable for use in a variety of fieldbus systems such as DIN measuring bus, BITBUS (IEEE 1118), Local Operating Network (LON) SUCOnet P, Modulink-P, P-VariNet, FIP ...    and INTERBUS - as remote bus cable (Type RBC) or installation remote bus with integrated power supply (type INBC) in the field of production automation, for high flexible applications (e.g. power chains, gantry robots, pick and place units, conveyors, machine tools, automated production systems, etc.)

Selected item
Item no.: Description:
2003666 MULTIBUS SK-C-PUR FRNC UL/CSA 2X2X0,25 VIOLET, cULus CMX
Variants
Filter
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
fixed installation flexible use continuously dynamic, high flexible use Drag chain
MULTIBUS & INTERBUS 100 - 120 Ohm - HF UL/CSA -high flexible - 2 X 2 X 0,25 2003666
BUS | FIELDBUS cables for industrial & process automation
for high flexible applications (drag chain), UL/CSA
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "MULTIBUS & INTERBUS 100 - 120 Ohm - HF UL/CSA -high flexible -"
SPECIAL FEATURES
  • low adhesion
  • largely resistant to lubricants, coolants fluids and grease
  • oil-resistant: acc. to DIN EN 60811-2-1
  • UV-resistant
  • EMC compliant shielding
  • max. cable lengths for a bus segment acc.to PI at stated transmission rate:      MULTIBUS: 93,75kbit/s-max.1,2km | 187,5kbit/s-max.1km | 0,5Mbit/s-max.400m                          1,5 Mbit/s-max.200m | 12,0 Mbit/s-max.100m      INTERBUS: 0,5Mbit/s-max.400m
REMARKS
  • RoHS-compliant
  • DESINA-compliant (violet)
  • Compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • LABS/silicone-free (during production)
  • FRNC: Flame Retardant Non Corrosive, halogen-free
PRODUCT DETAILS
DESIGN
Conductor material bare copper strand
Conductor class super fine wired acc. to IEC 60228 cl. 6
Core insulation BUScores: Polyolefine, supply cores: PVC
Core identification BUScores: acc. to DIN 47100, supply cores: rd, bu, gnye
Stranding BUScores stranded to a pair
Overall stranding (INBC) BUSelem. a. supply cores stranded
Overall shield copper braid tinned
Outer sheath material PUR
Sheath colour violet RAL 4001 (VT)
ELECTRICAL PROPERTIES
Rated voltage AC IEC BUScores: 250 V (not for high voltage purposee); supply cores: 500 V
Testing voltage 1,5 kV
Loop resistance max. 159,8 Ω/km - 0,25 mm²: max. 39,0 Ω/km 1,0 mm²
Capacity max. 60 nF/km
Characteristic impedance MULTIBUS: 100 - 120 Ω; INTERBUS: 100 Ω +/- 15 Ω
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 5 x d
Min. bending radius moved 7,5 x d < 3mTL* | 15 x d ≥ 3mTL*,
Traverse length (m) - drag chain max. 10 m
Traverse speed (m/s) - drag chain self-supporting: 4 m/s
Acceleration (m/s²) - drag chain max. 5 m/s²
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] - 40 °C / +80 °C
Operat. temp. moved min/max [°C] - 30 °C / +70 °C
PROPERTIES IN CASE OF FIRE
Halogen-free acc. to IEC 60754-1 (FRNC Typen)
Burning behavior flame retardant acc. to IEC 60332-1-2; CMX: acc. to IEC 60332-1-2, VW-1