PUR control cables, hand-held equipment cables
KAWEFLEX® CONTROL YPUR
01.04.05
|
as power, control and connecting cable in electrical systems and hand-held power tools, for fixed installation and flexible applications with free movement without tensile stress and without forced routing. Suitable for use in dry, humid and wet rooms. Outdoor use within the temperature range, but no laying underground.
Filter according to your requirements.
PUR control cables, hand-held equipment cables
PUR control cables, hand-held equipment cables
PUR control cables, hand-held equipment cables
SPECIAL FEATURES
- increased oil-resistant special two-layer outer sheath, resistant to acids, alkalis, solvents, hydrolysis, microbes, fats, etc.
- UV-resistant according to EN ISO 4892-2-2006, method A (colour change permitted)
- Ozone-resistant acc. to EN 50396 method B
- increased abrasion and cut resistance, notch-resistant, tear-resistant
- integrated wear indicator - damage to the grey outer jacket is visible through the black inner jacket underneath.
- more safety and efficiency in industrial and manual stripping
REMARKS
- RoHS compliant
- Compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
- LABS/silicon-free (during production)
- Special versions, other dimensions, cross-sections, wire and sheath colors are available on request.
PRODUCT DETAILS
DESIGN
| Conductor material | bare copper strand |
|---|---|
| Conductor class | acc. to IEC 60228 cl. 5 |
| Core insulation | PVC |
| Core identification | acc. to DIN VDE 0293 black cores with white numerals, G: with GNYE |
| Stranding | stranded in layers |
| Outer sheath material | YPUR - two-layer jacket |
| Outer sheath properties | PVC functional layer, black, crotches filled extruded under PUR outer jacket |
| Sheath colour | grey RAL 7001 |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | Uo/U: 300/500 V |
|---|---|
| Testing voltage | 4 kV |
| Conductor resistance | acc. to IEC 60228 cl. 5 |
| Insulation resistance | min. 20 MΩ x km |
| Current carrying capacity | acc. to. DIN VDE, see Technical Guidelines |
MECHANICAL & DYNAMIC PROPERTIES
| Min. bending radius fixed | 4 x d |
|---|---|
| Min. bending radius moved | 12,5 x d |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -40 °C / +80 °C |
|---|---|
| Operat. temp. moved min/max [°C] | -15 °C / +70 °C |
| Temp. at conductor in operation max [°C] | +70 °C in operation; +150 °C in case of short-circuit |