Instrumentation cables
INDULINE® RE-2X(ST)YSWBY-FL
02.08.03.01
|
Instrumentationcable for optimal, lossless transmission of analogous and digital signals in measurement and process control technology. Suitable for intrinsically safe systems zone 1 and zone 2 group II classified areas acc. IEC 60079-14. Suitable for dry and humid rooms as well as outdoor use and laying underground.
Filter according to your requirements.
Instrumentation cables
Properties
| Number of cores | 8 |
|---|---|
| Outer sheath material | PVC |
| Cross section | 0,75 |
Instrumentation cables
Properties*
| Number of cores | 8 |
|---|---|
| Outer sheath material | PVC |
| Cross section | 0,75 |
Instrumentation cables
Properties*
| Number of cores | 8 |
|---|---|
| Outer sheath material | PVC |
| Cross section | 0,75 |
Instrumentation cables
Properties*
| Number of cores | 8 |
|---|---|
| Outer sheath material | PVC |
| Cross section | 1,3 |
Instrumentation cables
Properties*
| Number of cores | 8 |
|---|---|
| Outer sheath material | PVC |
| Cross section | 1,3 |
Filter according to your requirements.
Indoor telecommunication & Fire alarm cables
Outdoor telecommunication cables
Outdoor telecommunication cables
Instrumentation cables
SPECIAL FEATURES
- more steady at higher frequencies and temperatures (+90°C) by XLPE core insulation (cross-linked PE)
- high crosstalk and low cable attenuation
- largely resistant to acids, bases and usual oils
- Oil resitance: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3
- triple protection for high mechanical requirements and magnetic shield (oxidationproofed steel wire braid and additional inner sheath)
- suitable for intrinsically safe systems zone 1+2 group II acc. IEC 60079-14
- Sunlight resitance: UL 1581 Section 1200
- flame-retardant acc. IEC 60332-1 and IEC 60332-3-24 (Cat. C)
REMARKS
- RoHS-compliant, compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
- Special versions e.g. fire-resistant (mica), halogen-free, oil and chemical-resistant (lead sheath or GuardSheath - lead-free), BS 5308, MESC etc. can be manufactured on request >> also available as compensating cable > INDUTHERM <.
PRODUCT DETAILS
DESIGN
| Conductor material | bare copper strand |
|---|---|
| Conductor class | 7-wired construction acc. to IEC 60228 cl. 2 |
| Core insulation | XLPE (cross-linked polyethylene) |
| Core identification | pairs: single-coloured with numerals: core A black, core B: white; triple: core A: white, core B: red, core C: black, core A and C with numerals |
| Stranding | pairs stranded in layers |
| Shielding | plastic clad aluminium foil (24 μm) with subjacent tinned drain wire 0,5mm² (7x0.30 mm) |
| Inner sheath material | PVC, black |
| Overall shield | steel wire braid, galvanized (SWB) |
| Outer sheath material | PVC |
| Sheath colour | black or blue RAL 5015 for intrinsically safe systems |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | 300 V |
|---|---|
| Testing voltage | 1,5 kV |
| Conductor resistance | 0.5mm²: max.36.7 Ω/km; 0.75mm²: max.25.0 Ω/km; 1.3mm²: max.14.2 Ω/km |
| Insulation resistance | min. 5 GΩ x km |
| Current carrying capacity | acc. to DIN VDE, s. Techn. Guidelines |
| Capacity | max.115 nF/km |
| Inductivity | ca. 1 mH/km |
| Coupling | max. 500 pF/500 m |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -40°C / +70°C |
|---|---|
| Operat. temp. moved min/max [°C] | - 5°C / +50°C |