Indoor Outdoor Direct burial
Shielded UV-resistant Increased oil resistance
CE CPR Class - Eca
fixed installation
Instrumentation cables

INDULINE® RE-2X(ST)YSWAY-FL PIMF

02.08.06.01

|

Application

Instrumentationcable for optimal, lossless transmission of analogous and digital signals in measurement and process control technology. Suitable for intrinsically safe systems zone 1 and zone 2 group II classified areas acc. IEC 60079-14. Suitable for dry and humid rooms as well as outdoor use and laying underground.

Selected item
Item no.: Description:
2001397 INDULINE RE-2X(ST)YSWAY-FL PIMF 4X2X0,75 BK,FLAME RETARDANT,EN 50288-7
Variants
Filter
TKD SmartFit+ automatically finds technically equivalent or better alternatives to a searched product. Performance, quality, and compatibility are taken into account—for cases in which the highest requirements must be met or exceeded.
Filter

Filter according to your requirements.

fixed installation
INDULINE® RE-2X(St)Yv-fl 4 X 2 X 0,75 2000115
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
10/10
We recommend this product as a suitable alternative!
fixed installation
INDULINE® RE-2X(St)Yv-fl 4 X 2 X 0,75 2000114
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
6/10
We recommend this product as a suitable alternative!
fixed installation
INDULINE® RE-2X(St)Yv-fl PIMF 4 X 2 X 1,3 2000313
Instrumentation cables
300V, shielded, +90C, pairs in metal foil, EN50288-7, CPR Eca
1/10
We recommend this product as a suitable alternative!
fixed installation
INDULINE® RE-2X(St)Yv-fl 4 X 2 X 1,3 2000117
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
1/10
We recommend this product as a suitable alternative!
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
Filter

Filter according to your requirements.

fixed installation
J-Y(St)Y Lg 4 X 2 X 0,6 2000194
Indoor telecommunication & Fire alarm cables
VDE0815, 300V, shielded, CPR Eca
fixed installation
A-2Y(L)2Y St III Bd , A-2YF(L)2Y St III Bd 4 X 2 X 0,6 2003334
Outdoor telecommunication cables
VDE0816, 300V, shielded, UV-resistant
fixed installation
A-2Y(L)2Y St III Bd , A-2YF(L)2Y St III Bd 4 X 2 X 0,6 2000029
Outdoor telecommunication cables
VDE0816, 300V, shielded, UV-resistant
fixed installation
INDULINE® RE-2X(ST)YSWAY-FL 4 X 2 X 0,75 2001357
Instrumentation cables
300V, shielded, +90C, steel wire armour, EN50288-7, CPR Eca
fixed installation
INDULINE® RE-2X(ST)YSWBY-FL 4 X 2 X 0,75 2001277
Instrumentation cables
300V, shielded, +90C, steel wire braid, EN50288-7, CPR Eca
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "INDULINE® RE-2X(ST)YSWAY-FL PIMF "
SPECIAL FEATURES
  • more steady at higher frequencies and temperatures (+90°C) by XLPE core insulation (cross-linked PE)
  • high crosstalk and low cable attenuation
  • single element & overall shield
  • largely resistant to acids, bases and usual oils
  • protection for high mech. requirements and magnetic shield (galvanized round or flat steel-wires, additional inner sheath)
  • Oil resistance: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3
  • Sunlight resitance: UL 1581 Section 1200
  • flame-retardant acc. IEC 60332-1-2 and IEC 60332-3-24 (Cat. C)
REMARKS
  • RoHS-compliant; compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • for intrinsically safe applications in Zone 1+2 of Group II in accordance with IEC 60079-14
  • Special versions e.g. fire-resistant (mica), halogen-free, oil and chemical-resistant (lead sheath or GuardSheath - lead-free), BS 5308, MESC etc. are available on request >> also available as compensating cable > INDUTHERM <.
PRODUCT DETAILS
DESIGN
Conductor material bare copper strand
Conductor class 7-wired construction acc.to IEC 60228 cl.2
Core insulation XLPE (cross-linked polyethylene)
Core identification pairs pairs: single-coloured with numerals: core A: black, core B: white; triple: single-coloured, core A: white, core B: red, core C: black, core A and C with numerals
Stranding pairs stranded in layers
Element shielding pairs in metal foil (PiMf) with subjacent tinned drain wire 0.6mm
Shielding plastic clad aluminium foil (24 μm) with subjacent tinned drain wire 0,5mm² (7x0.30 mm)
Inner sheath material PVC, black
Overall shield galvanized round or flat steel-wires (SWA)
Outer sheath material PVC
Sheath colour black or blue RAL 5015 for intrinsically safe systems
ELECTRICAL PROPERTIES
Rated voltage AC IEC 300 V
Testing voltage 1,5 kV
Conductor resistance 0.5mm²:max.36.7 Ω/km;0.75mm²:max.25.0 Ω/km;1.3mm²:max.14.2 Ω/km
Insulation resistance min. 5 GΩ x km
Current carrying capacity acc. to DIN VDE, s. Techn. Guidelines
Capacity max.115 nF/km
Inductivity ca. 1 mH/km
Coupling max. 500 pF/500 m
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40°C / +70°C
Operat. temp. moved min/max [°C] -5°C / +50°C