Indoor Outdoor Direct burial
Shielded UV-resistant Increased oil resistance
CE CPR Class - Eca
fixed installation
Instrumentation cables

INDULINE® RE-2X(ST)YSWAY-FL

02.08.05.01

|

Application

Instrumentationcable for optimal, lossless transmission of analogous and digital signals in measurement and process control technology. Suitable for intrinsically safe systems zone 1 and zone 2 group II classified areas acc. IEC 60079-14. Suitable for dry and humid rooms as well as outdoor use and laying underground.

Selected item
Item no.: Description:
2001468 INDULINE RE-2X(ST)YSWAY-FL 2X2X1,3 BLUE, FLAME RETARDANT, EN 50288-7
Variants
Filter
TKD SmartFit+ automatically finds technically equivalent or better alternatives to a searched product. Performance, quality, and compatibility are taken into account—for cases in which the highest requirements must be met or exceeded.
Filter

Filter according to your requirements.

fixed installation
INDULINE® RE-2X(St)Yv-fl 2 X 2 X 1,3 2000112
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
10/10
We recommend this product as a suitable alternative!
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
Filter

Filter according to your requirements.

fixed installation
INDULINE® RE-2X(St)Yv-fl 2 X 2 X 1 2000533
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
fixed installation
INDULINE® RE-2X(St)Yv-fl PIMF 2 X 2 X 1 2001248
Instrumentation cables
300V, shielded, +90C, pairs in metal foil, EN50288-7, CPR Eca
fixed installation
INDULINE® RE-2X(St)Yv-fl PIMF 2 X 2 X 1 2001247
Instrumentation cables
300V, shielded, +90C, pairs in metal foil, EN50288-7, CPR Eca
fixed installation
INDULINE® RE-2X(St)Yv-fl 2 X 2 X 1 2000582
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
fixed installation
INDULINE® RE-2X(St)Yv-fl 2 X 2 X 1,3 2000111
Instrumentation cables
300V, shielded, +90C, EN50288-7, CPR Eca
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "INDULINE® RE-2X(ST)YSWAY-FL "
SPECIAL FEATURES
  • more steady at higher frequencies and temperatures (+90°C) by XLPE core insulation (cross-linked PE)
  • high crosstalk and low cable attenuation
  • largely resistant to acids, bases and usual oils; Standard EN 50288-7
  • protection for high mech. requirements and magnetic shield (galvanized round or flat steel-wires, additional inner sheath)
  • oil resistance: ICEA S-73-532 / NEMA WC 57-2004 § 6.9.3
  • Sunlight resitance: UL 1581 Section 1200
  • flame-retardant acc. IEC 60332-1-2 and IEC 60332-3-24 (Cat. C)
REMARKS
  • RoHS-compliant; compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • for intrinsically safe applications in Zone 1+2 of Group II in accordance with IEC 60079-14
  • Special versions e.g. fire-resistant (mica), halogen-free, oil and chemical-resistant (lead sheath or GuardSheath - lead-free), BS 5308, MESC etc. are available on request >> also available as compensating cable > INDUTHERM <.
PRODUCT DETAILS
DESIGN
Conductor material bare copper strand
Conductor class 7-wired construction acc. to IEC 60228 cl. 2
Core insulation XLPE (cross-linked polyethylene)
Core identification pairs pairs: single-coloured with numerals: core A: black, core B: white; triple: single-coloured, core A: white, core B: red, core C: black, core A and C with numerals
Stranding pairs stranded in layers
Shielding plastic clad aluminium foil (24 μm) with subjacent tinned drain wire 0.5mm² (7x0.30 mm)
Inner sheath material PVC, black
Overall shield galvanized round or flat steel-wires (SWA)
Outer sheath material PVC
Sheath colour black or blue RAL 5015 for intrinsically safe systems
ELECTRICAL PROPERTIES
Rated voltage AC IEC 300 V
Testing voltage core/core (AC/DC): 1.5 / 2 kV (duration 1 minute)
Conductor resistance 0.5mm²: max.36.7 Ω/km; 0.75mm²: max.25.0 Ω/km; 1.3mm²: max.14.2 Ω/km
Insulation resistance min. 5 GΩ x km
Current carrying capacity acc. to DIN VDE, s. Techn. Guidelines
Capacity max.115 nF/km
Inductivity ca. 1 mH/km
Coupling max. 500 pF/500 m
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40°C / +70°C
Operat. temp. moved min/max [°C] -5°C / +50°C