H05VVC4V5-K 61G0,75 - 300/500 V, GREY RAL 7001 | M0002855_1003474
Approved PVC control cables

H05VVC4V5-K HAR

01.02.02

|

Application
power, control and connecting cable in electrical facilities for lossless data and signal transmission, fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry, humid, wet rooms (also water-oil mixture). Outdoor use only with UV-protection, no laying underground.
Selected item
Item no.: Description:
1003474 H05VVC4V5-K 61G0,75 300/500 V, GREY RAL 7001
Article Name
Variants
Item no. Dimension Outer-Ø [mm] nom. Cu Index [kg/km] Weight [kg/1.000]
"H05VVC4V5-K HAR "
SPECIAL FEATURES
  • increased resistance to oil by special PVC outer sheath, largely resistant to acids and bases acc. to EN 50363-4-1
  • additional mechanical protection by inner sheath
  • EMC compliant shielding
  • HAR-approval for Europe
REMARKS
  • RoHS compliant
  • Compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • LABS-free/silicone-free (during production)
  • Special versions, other dimensions, cross-sections, wire and sheath colors are available on request.
DESIGN
Conductor material bare copper strand
Conductor class acc. to IEC 60228 cl. 5
Core insulation PVC
Core identification acc. to DIN VDE 0293 black cores with white numerals; G = with GNYE
Stranding stranded in layers
Inner sheath material PVC
Overall shield copper braid tinned, coverage approx. 85 %
Outer sheath material PVC
Sheath colour grey, RAL 7001
ELECTRICAL PROPERTIES
Rated voltage AC IEC Uo/U: 300/500 V
Testing voltage 3 kV
Conductor resistance acc. to IEC 60228 cl. 5
Insulation resistance min. 20 MΩ x km
Current carrying capacity acc. to. DIN VDE | acc. to DIN VDE
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 6 x d
Min. bending radius moved 12,5 x d
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40 °C / +70 °C
Operat. temp. moved min/max [°C] -5 °C / +70 °C
Temp. at conductor in operation max [°C] +70 °C in operation; +150 °C in case of short-circuit
STANDARDS & APPROVALS
Standard EN 50525-2-51 / VDE 0285-525-2-51
Approvals HAR

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.
KAWEFLEX® Allround 7110 SK-PVC UL/CSA 04.11.05
Control cables for use in drag chains
for increased requirements, 300/500V, unshielded, UL/CSA
Item count 47
KAWEFLEX® Allround 7720 SK-TP-C-PUR UL/CSA 04.15.10
Electronic cables for use in drag chains
for high requirements, 300V, shielded, halogen-free, UL/CSA
Item count 24
NYCY 0,6/1kV 09.07.02
Power Cables
0,6/1kV, shielded, UV-resistant, direct burial, VDE, CPR Eca
Item count 47
AUTO B - RADOX® Databus 155S RW/REMS 20.10.04
BUS data cables for automotive
Item count 1