FLAME-OZ-CH FRNC 0,6/1 kV - B2ca - 2X1 - BLACK RAL 9005 | M0013317_T40000604
Indoor Outdoor
Shielded UV-resistant Halogen-free Flame retardant
CE EAC CPR Class - B2ca
fixed installation flexible use
Halogen-free control cables

FLAME-JZ/OZ-CH FRNC 0,6/1kV - B2ca

01.03.02.04

|

Application

shielded halogen-free and environmentally power, control and connecting cable in electrical facilities, in fire vulnerable areas and facilities with high concentration of people and property values, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry and humid rooms. Suitable for use in dry and damp rooms as well as outdoors, but not for direct burial.

Selected item
Item no.: Description:
T40000604 FLAME-OZ-CH FRNC 0,6/1 kV - B2ca 2X1 BLACK RAL 9005
Variants
Filter
There are currently no available alternative products.
PRODUCT INFO "FLAME-JZ/OZ-CH FRNC 0,6/1kV - B2ca "
SPECIAL FEATURES
  • FRNC (Flame Retardant, Non Corrosive)
  • LSF 0H ( Low smoke in fume, zero halogen)
  • improved behaviour in case of fire (acc. to IEC 60332-3-25 Cat. A)
  • recommended for EMC-applications
  • UV-resistant outer sheath
REMARKS
  • RoHS compliant
  • compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • LABS-free/silicone-free (during production)
PRODUCT DETAILS
DESIGN
Conductor material bare copper strand
Conductor class acc. to IEC 60228 cl. 5
Core insulation special halogen-free compound
Core identification acc. to DIN VDE 0293 black cores with white numerals; G = GNYE
Stranding stranded in layers
Overall shield copper braid tinned; coverage approx. 85 %
Outer sheath material special halogen-free compound
Sheath colour black, RAL 9005
ELECTRICAL PROPERTIES
Rated voltage AC IEC 0,6/1 kV | Uo/U: 600/1000 V
Testing voltage 6 kV | 6 kV
Conductor resistance acc. to IEC 60228 cl. 5
Insulation resistance min. 20 MΩ x km
Current carrying capacity acc. to DIN VDE, see technical Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 4 x d
Min. bending radius moved 12.5 x d
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40 °C / +70 °C
Operat. temp. moved min/max [°C] -15 °C / +70 °C
PROPERTIES IN CASE OF FIRE
Halogen-free acc. to IEC 60754-1
Smoke density acc. to IEC 61034-2
Corrodibility acc. to IEC 60754-2
Burning behavior halogen-free and flame-retardant acc. to IEC 60332-1-2 and IEC 60332-3-24 Cat. C resp. IEC 60332-3-25 Cat. A