FLAME-JZ-H FRNC 0,6/1kV - B2ca - 4G16 - BLACK RAL 9005 | M0013313_T40000591
Halogen-free control cables

FLAME-JZ/OZ-H FRNC 0.6/1KV - Cca or B2ca

01.03.01.04

|

Application
halogen-free and environmentally power, control and connecting cable in electrical facilities, in fire vulnerable areas and facilities with high concentration of people and property values, for fixed laying and flexible applications without tensile stress and without defined cable routing. Suitable for use in dry and humid rooms. Suitable for use in dry and damp rooms as well as outdoors, but not for direct burial.
Selected item
Item no.: Description:
T40000591 FLAME-JZ-H FRNC 0,6/1kV - B2ca 4G16 BLACK RAL 9005
Variants
Item no. Dimension Outer-Ø [mm] nom. Cu Index [kg/km] Weight [kg/1.000]
"FLAME-JZ/OZ-H FRNC 0.6/1KV - Cca or B2ca "
SPECIAL FEATURES
  • FRNC (Flame Retardant, Non Corrosive)
  • LSF 0H ( Low smoke in fume, zero halogen)
  • improved behaviour in case of fire (acc. to IEC 60332-3-25 Cat. A)
  • UV-resistant outer sheath
REMARKS
  • RoHS compliant
  • compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • LABS-free/silicone-free (during production)
DESIGN
Conductor material bare copper strand
Conductor class acc. to IEC 60228 cl. 5
Core insulation special halogen-free compound
Core identification acc. to DIN VDE 0293 black cores with white numerals; G = GNYE
Stranding stranded in layers
Outer sheath material special halogen-free compound
Sheath colour black, RAL 9005
ELECTRICAL PROPERTIES
Rated voltage AC IEC Uo/U: 600/1000 V
Testing voltage 6 kV | 6 kV
Conductor resistance acc. to IEC 60228 cl. 5
Insulation resistance min. 20 MΩ x km
Current carrying capacity acc. to DIN VDE, see technical Guidelines
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 4 x d
Min. bending radius moved 12.5 x d
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40 °C / +70 °C
Operat. temp. moved min/max [°C] -15 °C / +70 °C
PROPERTIES IN CASE OF FIRE
Halogen-free acc. to IEC 60754-1
Smoke density acc. to IEC 61034-2
Corrodibility acc. to IEC 60754-2
Burning behavior halogen-free and flame-retardant acc. to IEC 60332-1-2 and IEC 60332-3-24 Cat. C resp. IEC 60332-3-25 Cat. A
CPR - fire class Cca | B2ca
CPR - acidity class a1
CPR - drop behaviour class d1
CPR - smoke density class s1a
CPR - declared Performance Cca / B2ca - s1a, d1, a1
CPR - System 1+
CPR - notified body(s) 0051

Please enter a valid email address.
Please enter a valid question.
Fields marked with * are mandatory.
KAWEFLEX® Allround 7110 SK-PVC UL/CSA 04.11.05
Control cables for use in drag chains
for increased requirements, 300/500V, unshielded, UL/CSA
Item count 47
KAWEFLEX® Allround 7720 SK-TP-C-PUR UL/CSA 04.15.10
Electronic cables for use in drag chains
for high requirements, 300V, shielded, halogen-free, UL/CSA
Item count 24
NYCY 0,6/1kV 09.07.02
Power Cables
0,6/1kV, shielded, UV-resistant, direct burial, VDE, CPR Eca
Item count 47
AUTO B - RADOX® Databus 155S RW/REMS 20.10.04
BUS data cables for automotive
Item count 1