DeviceNet™ C-PVC TRUNK UL/CSA 1X2XAWG18+1X2XAWG15 - VIOLET, cULus CMG | M0006091_2003694
Indoor Outdoor
Shielded UV-resistant Oil resistant
CE CSA
fixed installation
BUS | FIELDBUS cables for industrial & process automation

DeviceNet 120 Ohm UL/CSA

03.10.04.01

|

Application
as fieldbus cables for DeviceNet™ systems in the field of production automation for reliable data and energy transmission (e.g. between sensors, actuators and controllers), for fixed installation & flexible applications. DeviceNet™ is an Allen Bradley (Rockwell Automation) developed, based on proven CAN technology bus system. Standard acc. ODVA specifications  
Selected item
Item no.: Description:
2003694 DeviceNet™ C-PVC TRUNK UL/CSA 1X2XAWG18+1X2XAWG15 VIOLET, cULus CMG
Variants
Filter
TKD CoreFit offers functional alternatives that cover the core benefits of the original product—often with reduced functionality or simpler design, but at a lower price.
fixed installation
DeviceNet 120 Ohm UL/CSA 03.10.04.01
BUS | FIELDBUS cables for industrial & process automation
for fixed installation & limited flexible applications, UL/CSA
Despite careful pre-evaluation of our alternatives, we ask you to review the selection based on your requirements. Our recommendations include at least equivalent, and in some cases better, properties.
PRODUCT INFO "DeviceNet 120 Ohm UL/CSA "
SPECIAL FEATURES
  • largely resistant to grease, coolant fluids and lubricants
  • oil-resistant: acc. to DIN EN 60811-2-1 (only mineral oil)
  • UV-resistant
  • optimized EMC compliant shielding
  • max. cable lengths for a bus segment at stated transmission rate assupply cable:   Trunk - thick: 125 kbit/s-max.500m | 250 kbit/s-max.250m | 0,5 Mbit/s-max.100m                    Drop - thin   : 125 kbit/s-max.100m | 250 kbit/s-max.100m | 0,5 Mbit/s-max.100m
REMARKS
  • RoHS-compliant
  • DESINA-compliant (violet)
  • Compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
  • LABS/silicon-free (during production)
  • ODVA - Open DeviceNet Vendors Association
PRODUCT DETAILS
DESIGN
Conductor material copper strand tinned
Conductor class 19-wired
Core insulation BUScores: foamed PE, supply cores: PVC
Core identification BUScores: bu, wh; supply cores: rd, bk
Stranding cores twisted to pairs
Element shielding pairs in aluminium clad foil, cover. 100%
Overall stranding pairs stranded in layers
Overall shield copper braid tinned, with subjacent tinned drain wire
Outer sheath material PVC
Sheath colour violet RAL 4001 (VT) or grey RAL 7001 (GY)
ELECTRICAL PROPERTIES
Rated voltage AC IEC 300 V (not for high voltage purposee)
Testing voltage 1,5 kV
Loop resistance max. 181,8 Ω/km - AWG24, max. 114,8 Ω/km - AWG22, max. 45,4 Ω/km - AWG18, max. 22,6 Ω/km - AWG15
Capacity nom. 40 nF/km
Characteristic impedance 120 Ω +/- 12 Ω
MECHANICAL & DYNAMIC PROPERTIES
Min. bending radius fixed 7,5 x d
Min. bending radius moved 15 x d
THERMAL PROPERTIES
Operat. temp. fixed min./max. [°C] -40 °C / +80 °C
Operat. temp. moved min/max [°C] -10 °C / +70 °C