BUS | FIELDBUS cables for industrial & process automation
ASi-BUS Actuator Sensor Interface UL/CSA
03.10.06.01
|
as fieldbus cables for ASi (Actuator Sensor Interface) systems, in the field of factory automation, for connecting devices to the lowest field level (sensors, actuators), for fixed installation & flexible applications. Data and energy are transmitted via an unscreened, geometrically coded two-core flat cable. Standard acc. to EN 50295 / IEC 62026
BUS | FIELDBUS cables for industrial & process automation
SPECIAL FEATURES
- special geometry prevents incorrect contacting (reverse polarity protection)
- simple & quick installation without tools (piercing technology)
- oil resistant: acc. to DIN EN 60811-2-1
- UV-resistant: black versions (PVC)
REMARKS
- RoHS compliant
- Compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
- LABS/silicone-free (during production)
- EPDM-H: halogen-free
- LD - Long Distance
PRODUCT DETAILS
DESIGN
| Conductor material | copper strand tinned |
|---|---|
| Conductor class | super fine wire, acc. to IEC 60228 cl. 6 |
| Core insulation | EPDM resp. TPE |
| Core identification | blue, brown |
| Outer sheath material | EPDM, TPE resp. PVC |
| Sheath colour | yellow RAL 1023 (YE) or black RAL 9005 (BK) |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | 300 V (not for high voltage purposes) |
|---|---|
| Testing voltage | 2 kV |
| Conductor resistance | 13,7 Ω/km - 1,5mm²; 8,21 Ω/km 2,5 mm² |
| Capacity | nom. 80 nF/km |
MECHANICAL & DYNAMIC PROPERTIES
| Min. bending radius fixed | 12 mm |
|---|---|
| Min. bending radius moved | 24 mm |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -40 °C / +105 °C (EPDM+TPE) | -40 °C / + 90 °C (PVC) |
|---|---|
| Operat. temp. moved min/max [°C] | -30 °C / +105 °C (EPDM+TPE) | -20 °C / + 90 °C (PVC) |
PROPERTIES IN CASE OF FIRE
| Halogen-free | acc. to IEC 60754-1 (EPDM-H types) |
|---|---|
| Burning behavior | TPE: FH2-25 (IEC 707), Horizontal Flame Test (UL 2556) | PVC CMG: IEC 60332-3-24(Cat.C), FT4 |