Cables for servo-drives
KAWEFLEX® SERVO 2XSL(St)CY... & 2XSL(St)CYK... 0,6/1 kV EMV
05.01.32
|
power, control and connecting cable for drive systems with frequency converter technology, for fixed laying and casually movement without tensile stress and without defined cable routing. Suitable for use in dry, humid and wet rooms. Outdoor use (only K-version), but no laying underground.
Filter according to your requirements.
Cables for servo-drives
Cables for servo-drives
Filter according to your requirements.
Cables for servo-drives
Cables for servo-drives
Cables for servo-drives
SPECIAL FEATURES
- largely resistant to acids, bases and specified types of oil
- max. perm. current carrying capacity at 30 ° C ambient temperature.
- low operating capacity, low coupling resistance
- black version with UV-resistant, flexible at low temp. outer sheath
- enables trouble-free operation of frequency converters through optimum EMC compliant shielding
- low capacitance enables longer cable lengths between motor and frequency converter
- increased power transmission with the same conductor cross-section compared to standard 2YSL(St)CY versions
REMARKS
- RoHS-compliant, compliant with the 2014/35/EU Directive (''Low Voltage Directive'') CE
- LABS/silicon-free (during production)
- Special versions, e.g. for direct burial 2XSL(St)CYK-J DB 0.6/1 kV EMV (DB = direct burial), other dimensions, cross-sections, core and sheath colors can be manufactured on request.
PRODUCT DETAILS
DESIGN
| Conductor material | bare copper strand |
|---|---|
| Conductor class | acc. to IEC 60228 cl. 5 |
| Core insulation | XLPE |
| Core identification | acc. to DIN VDE 0293-308 coloured cores with GNYE |
| Stranding | stranded in layers |
| Overall shield | alu-lamin. polyester foil, metal side outside, cover. 100% under copper braid tinned |
| Outer sheath material | PVC |
| Sheath colour | transparent; K-version: black |
ELECTRICAL PROPERTIES
| Rated voltage AC IEC | Uo/U 0,6/1 kV - highest permissible operating voltage Single phase and three-phase: 700/1200 V, DC operation: 900/1800 V |
|---|---|
| Testing voltage | 4 kV |
| Conductor resistance | acc. to IEC 60228 cl. 5 |
| Insulation resistance | min. 200 MΩ x km |
| Current carrying capacity | look at the table on the right side |
| Capacity | look at the table on the right side |
MECHANICAL & DYNAMIC PROPERTIES
| Min. bending radius fixed | ≤ 12mm Ø: 5 x d; ≤ 20mm Ø: 7,5 x d; > 20mm Ø: 10 x d |
|---|---|
| Min. bending radius moved | ≤ 12mm Ø: 10 x d; ≤ 20mm Ø: 15 x d; > 20mm Ø: 20 x d |
THERMAL PROPERTIES
| Operat. temp. fixed min./max. [°C] | -40 °C / +90 °C |
|---|---|
| Operat. temp. moved min/max [°C] | -5 °C / +90°C, K-version: -15 °C / +90°C |
| Temp. at conductor in operation max [°C] | + 90 °C in operation; +250 °C in case of short-circuit |